The working principle of the constant pressure water pump is as follows:
- The VFD drives the water pump, and the pressure sensor/transmitter feeds back the pressure signal to the VFD to form a closed loop system.
- When the water pipe pressure is less than the set value, the VFD wakes up and starts pumping water.
- When the pressure does not reach the set target, the operating frequency will continue to increase to the rated frequency of the pump.
- When the pressure is greater than the set pressure, the operating frequency will decrease.
- When the pressure is greater than the sleep pressure, the frequency decreases to the sleep frequency for a period of time, and then stops pumping water.
- When the pressure is lower than the wake-up pressure, the pump starts to run again.